An Online UPS output is independent of voltage and frequency variations of the mains.
Offers the highest level of critical load protection as the load is supplied with closely regulated power at all times
Has a load break of less than 5ms when transferring between inverter and bypass
Is totally transparent to the load in the case of a mains failure
Is the most expensive capital cost of UPS systems
Has a higher running cost than other types of system, as the rectifier and inverter are permanently on load.
Features: | ||||||||||||
1. The overall efficiency is as high as 98%; Provide ECO mode, achieving efficiency of over 99% and reducing power loss of UPS. 2. Design to meet the requirements of the power grid and provide a wide input voltage range of 210VAC~475VAC. Suitable for harsh power grid environments. The excellent input frequency range enables UPS to adapt to different power supply devices such as generators. 3. IGBT frequency modulation intelligent rectification and inversion technology, with an input power factor of up to 0.99 and input current harmonics as low as 3%; The output voltage and current performance are more excellent. 4. Powerful overload capacity: 110-125% load can operate normally for 10 minutes; 125-150% load can operate normally for 1 minute. And has the ability to output short circuit protection. | ||||||||||||
Parameters:
Model | HSS1101 | HSS1102 | HSS1103 | HSS1106 | HSS1110 | HSS1115 |
Capacity | 1KVA | 2KVA | 3KVA | 6KVA | 10KVA | 15KVA |
Standard Battery Configured | 12V/7AH*2 | 12V/7AH*3/4 | 12V/7AH*4/6 | 12V/7AH*8/12 | 12V/7AH*16 | 12V/7AH*16 |
Extend BATT Qty | 2/3pcs | 2/6pcs | 4/8pcs | 8/16pcs | 16pcs | 16pcs |
Standard Dimension(mm) | 145*282*220 | 145*397*220 | 190*421*318 | 190*369*688 | 190*422*688 | 190*422*688 |
Extend unit Dimension | 145*282*220 | 145*397*220 | 145*397*220 | 190*369*318 | 190*442*318 | 190*442*318 |
Model | HTS3101 | HTS3115 | HTS3120 | |||
Capacity | 10KVA | 15KVA | 20KVA | |||
Standard Battery Configured | 12V/7AH*16 | |||||
Extend Battery | 16pcs | |||||
Dimension(mm) | 145*282*220 | 145*397*220 | 190*442*318 |
Model | HTT3310 | HTT3320 | HTT3330 | HTT3340 | HTT3360 | HTT3380 |
Capacity | 10KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA |
Battery Qty | 16pcs | 16pcs | 32pcs | 32pcs | 32pcs | 32pcs |
Dimension(mm) | 592*250*826 | 592*250*826 | 815*250*826 | 815*300*1000 | 790*360*1010 | |
Weight(kg) | 32 | 35 | 64 | 82 | 94 | 96 |
220VAC Input
Model item | HSS1101 | HSS1101S | HSS1102 | HSS1102S | HSS1103 | HSS1103S | HSS1106 | HSS1106S | HSS1110 | HSS1110S | |||||||||
Rated power | 1000VA/900W | 2000VA/1800W | 3000VA/2700W | 6kVA/5.4kW | 10kVA/9kW | ||||||||||||||
AC Input | Input system | Single phase (L/N+PE) | |||||||||||||||||
Nominal voltage | 208/220/230/240Vac | ||||||||||||||||||
Frequency | 50/60Hz | ||||||||||||||||||
Voltage range | 90~300VAC±5VAC | ||||||||||||||||||
Frequency range | (40~70)±0.5Hz | ||||||||||||||||||
Input power factor | >0.99 | ||||||||||||||||||
Bypass Voltage Range | 180~265VAC×(1±3%) | ||||||||||||||||||
Battery Input | Nominal Voltage | 24V | 36V | 48V | 72V | 72V | 96V | 192V | 192V | 192V/240V | |||||||||
Battery Capacity & Quantity | 12V/7AH x 2pcs | External | 12V/7AH x 4pcs | External | 12V/7AH x 6pcs | External | 12V/7AH x 16pcs | External | 12V/7AH x16/20pcs | External | |||||||||
Backup Time | Half loaded≥8minutes, Full loaded ≥3minutes(standard) | Half loaded≥6minutes, Full loaded ≥3minutes(standard) | |||||||||||||||||
Battery charger time | Charger to 90% battery capacity in 5 hours(standard) Dependent on the capacity of external batteries (long backup time) | ||||||||||||||||||
AC Output | Output wiring system | Single phase (L/N+PE) | |||||||||||||||||
Inverter Mode Output voltage | 208/220/230/240Vac±2% | ||||||||||||||||||
Waveform | Sine Wave | ||||||||||||||||||
Harmonic Distortion | THD<2% (linear load) THD<7% (nonlinear load) | ||||||||||||||||||
Output frequency | 50/60±4Hz (Sync mode) 50/60Hz±1% (Fix Freq. mode) | ||||||||||||||||||
Overload capability | 105~125%≥ 60s,126~150%≥30s The recover point is 70% | ||||||||||||||||||
Transfer time | Battery <-> Line Mode :0ms | ||||||||||||||||||
Efficiency | Line Mode | 86% | 88% | 89% | 92% | 93% | |||||||||||||
Battery Mode | 85% | 86% | 87% | ||||||||||||||||
Communications | RS232 RS485(optional), Dry contact(optional), Network Card(Option) | ||||||||||||||||||
Alarm Function | AC/DC input under abnormal, overload condition and Inverter problems | ||||||||||||||||||
Protection Function | AC input or output above or below the range of voltage, overload, over temperature and short circuit protection | ||||||||||||||||||
Noise | <50dB | <55dB | |||||||||||||||||
Model item | LSS1101 | LSS1101S | LSS1102 | LSS1102S | LSS1103 | LSS1103S | LSS1106 | LSS1106S | LSS1110 | LSS1110S | |||||||||
Rated power | 1000VA/900W | 2000VA/1800W | 3000VA/2700W | 6kVA/5.4kW | 10kVA/9kW | ||||||||||||||
AC Input | Input system | Single phase (L/N+PE) | |||||||||||||||||
Nominal voltage | 100/110/120/127Vac | ||||||||||||||||||
Frequency | 50/60Hz | ||||||||||||||||||
Voltage range | 55-145Vac±3VAC | ||||||||||||||||||
Frequency range | (40~70)±0.5Hz | ||||||||||||||||||
Input power factor | >0.99 | ||||||||||||||||||
Bypass Voltage Range | 80~140VAC×(1±3%) | ||||||||||||||||||
Battery Input | Nominal Voltage | 24V | 36V | 48V | 72V | 72V | 96V | 192V | 192V | 192V/240V | |||||||||
Battery Capacity & Quantity | 12V/7AH x 2pcs | External | 12V/7AH x 4pcs | External | 12V/7AH x 6pcs | External | 12V/7AH x 16pcs | External | 12V/7AH x16/20pcs | External | |||||||||
Backup Time | Half loaded≥8minutes, Full loaded ≥3minutes(standard) | Half loaded≥6minutes, Full loaded ≥3minutes(standard) | |||||||||||||||||
Battery charger time | Charger to 90% battery capacity in 5 hours(standard) Dependent on the capacity of external batteries (long backup time) | ||||||||||||||||||
AC Output | Output wiring system | Single phase (L/N+PE) | |||||||||||||||||
Inverter Mode Output voltage | 100/110/120/127Vac±2% | ||||||||||||||||||
Waveform | Sine Wave | ||||||||||||||||||
Harmonic Distortion | THD<2% (linear load) THD<7% (nonlinear load) | ||||||||||||||||||
Output frequency | 50/60±4Hz (Sync mode) 50/60Hz±1% (Fix Freq. mode) | ||||||||||||||||||
Overload capability | 105~125%≥ 60s,126~150%≥30s The recover point is 70% | ||||||||||||||||||
Transfer time | Battery <-> Line Mode :0ms | ||||||||||||||||||
Efficiency | Line Mode | 86% | 86% | 87% | 88% | 89% | |||||||||||||
Battery Mode | 85% | ||||||||||||||||||
Communications | RS232 RS485(optional), Dry contact(optional), Network Card(Option) | ||||||||||||||||||
Alarm Function | AC/DC input under abnormal, overload condition and Inverter problems | ||||||||||||||||||
Protection Function | AC input or output above or below the range of voltage, overload, over temperature and short circuit protection | ||||||||||||||||||
Noise | <50dB | <55dB |
Subject to change according to order, check the product name plate for specified battery voltage information.
An Online UPS output is independent of voltage and frequency variations of the mains.
Offers the highest level of critical load protection as the load is supplied with closely regulated power at all times
Has a load break of less than 5ms when transferring between inverter and bypass
Is totally transparent to the load in the case of a mains failure
Is the most expensive capital cost of UPS systems
Has a higher running cost than other types of system, as the rectifier and inverter are permanently on load.
Features: | ||||||||||||
1. The overall efficiency is as high as 98%; Provide ECO mode, achieving efficiency of over 99% and reducing power loss of UPS. 2. Design to meet the requirements of the power grid and provide a wide input voltage range of 210VAC~475VAC. Suitable for harsh power grid environments. The excellent input frequency range enables UPS to adapt to different power supply devices such as generators. 3. IGBT frequency modulation intelligent rectification and inversion technology, with an input power factor of up to 0.99 and input current harmonics as low as 3%; The output voltage and current performance are more excellent. 4. Powerful overload capacity: 110-125% load can operate normally for 10 minutes; 125-150% load can operate normally for 1 minute. And has the ability to output short circuit protection. | ||||||||||||
Parameters:
Model | HSS1101 | HSS1102 | HSS1103 | HSS1106 | HSS1110 | HSS1115 |
Capacity | 1KVA | 2KVA | 3KVA | 6KVA | 10KVA | 15KVA |
Standard Battery Configured | 12V/7AH*2 | 12V/7AH*3/4 | 12V/7AH*4/6 | 12V/7AH*8/12 | 12V/7AH*16 | 12V/7AH*16 |
Extend BATT Qty | 2/3pcs | 2/6pcs | 4/8pcs | 8/16pcs | 16pcs | 16pcs |
Standard Dimension(mm) | 145*282*220 | 145*397*220 | 190*421*318 | 190*369*688 | 190*422*688 | 190*422*688 |
Extend unit Dimension | 145*282*220 | 145*397*220 | 145*397*220 | 190*369*318 | 190*442*318 | 190*442*318 |
Model | HTS3101 | HTS3115 | HTS3120 | |||
Capacity | 10KVA | 15KVA | 20KVA | |||
Standard Battery Configured | 12V/7AH*16 | |||||
Extend Battery | 16pcs | |||||
Dimension(mm) | 145*282*220 | 145*397*220 | 190*442*318 |
Model | HTT3310 | HTT3320 | HTT3330 | HTT3340 | HTT3360 | HTT3380 |
Capacity | 10KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA |
Battery Qty | 16pcs | 16pcs | 32pcs | 32pcs | 32pcs | 32pcs |
Dimension(mm) | 592*250*826 | 592*250*826 | 815*250*826 | 815*300*1000 | 790*360*1010 | |
Weight(kg) | 32 | 35 | 64 | 82 | 94 | 96 |
220VAC Input
Model item | HSS1101 | HSS1101S | HSS1102 | HSS1102S | HSS1103 | HSS1103S | HSS1106 | HSS1106S | HSS1110 | HSS1110S | |||||||||
Rated power | 1000VA/900W | 2000VA/1800W | 3000VA/2700W | 6kVA/5.4kW | 10kVA/9kW | ||||||||||||||
AC Input | Input system | Single phase (L/N+PE) | |||||||||||||||||
Nominal voltage | 208/220/230/240Vac | ||||||||||||||||||
Frequency | 50/60Hz | ||||||||||||||||||
Voltage range | 90~300VAC±5VAC | ||||||||||||||||||
Frequency range | (40~70)±0.5Hz | ||||||||||||||||||
Input power factor | >0.99 | ||||||||||||||||||
Bypass Voltage Range | 180~265VAC×(1±3%) | ||||||||||||||||||
Battery Input | Nominal Voltage | 24V | 36V | 48V | 72V | 72V | 96V | 192V | 192V | 192V/240V | |||||||||
Battery Capacity & Quantity | 12V/7AH x 2pcs | External | 12V/7AH x 4pcs | External | 12V/7AH x 6pcs | External | 12V/7AH x 16pcs | External | 12V/7AH x16/20pcs | External | |||||||||
Backup Time | Half loaded≥8minutes, Full loaded ≥3minutes(standard) | Half loaded≥6minutes, Full loaded ≥3minutes(standard) | |||||||||||||||||
Battery charger time | Charger to 90% battery capacity in 5 hours(standard) Dependent on the capacity of external batteries (long backup time) | ||||||||||||||||||
AC Output | Output wiring system | Single phase (L/N+PE) | |||||||||||||||||
Inverter Mode Output voltage | 208/220/230/240Vac±2% | ||||||||||||||||||
Waveform | Sine Wave | ||||||||||||||||||
Harmonic Distortion | THD<2% (linear load) THD<7% (nonlinear load) | ||||||||||||||||||
Output frequency | 50/60±4Hz (Sync mode) 50/60Hz±1% (Fix Freq. mode) | ||||||||||||||||||
Overload capability | 105~125%≥ 60s,126~150%≥30s The recover point is 70% | ||||||||||||||||||
Transfer time | Battery <-> Line Mode :0ms | ||||||||||||||||||
Efficiency | Line Mode | 86% | 88% | 89% | 92% | 93% | |||||||||||||
Battery Mode | 85% | 86% | 87% | ||||||||||||||||
Communications | RS232 RS485(optional), Dry contact(optional), Network Card(Option) | ||||||||||||||||||
Alarm Function | AC/DC input under abnormal, overload condition and Inverter problems | ||||||||||||||||||
Protection Function | AC input or output above or below the range of voltage, overload, over temperature and short circuit protection | ||||||||||||||||||
Noise | <50dB | <55dB | |||||||||||||||||
Model item | LSS1101 | LSS1101S | LSS1102 | LSS1102S | LSS1103 | LSS1103S | LSS1106 | LSS1106S | LSS1110 | LSS1110S | |||||||||
Rated power | 1000VA/900W | 2000VA/1800W | 3000VA/2700W | 6kVA/5.4kW | 10kVA/9kW | ||||||||||||||
AC Input | Input system | Single phase (L/N+PE) | |||||||||||||||||
Nominal voltage | 100/110/120/127Vac | ||||||||||||||||||
Frequency | 50/60Hz | ||||||||||||||||||
Voltage range | 55-145Vac±3VAC | ||||||||||||||||||
Frequency range | (40~70)±0.5Hz | ||||||||||||||||||
Input power factor | >0.99 | ||||||||||||||||||
Bypass Voltage Range | 80~140VAC×(1±3%) | ||||||||||||||||||
Battery Input | Nominal Voltage | 24V | 36V | 48V | 72V | 72V | 96V | 192V | 192V | 192V/240V | |||||||||
Battery Capacity & Quantity | 12V/7AH x 2pcs | External | 12V/7AH x 4pcs | External | 12V/7AH x 6pcs | External | 12V/7AH x 16pcs | External | 12V/7AH x16/20pcs | External | |||||||||
Backup Time | Half loaded≥8minutes, Full loaded ≥3minutes(standard) | Half loaded≥6minutes, Full loaded ≥3minutes(standard) | |||||||||||||||||
Battery charger time | Charger to 90% battery capacity in 5 hours(standard) Dependent on the capacity of external batteries (long backup time) | ||||||||||||||||||
AC Output | Output wiring system | Single phase (L/N+PE) | |||||||||||||||||
Inverter Mode Output voltage | 100/110/120/127Vac±2% | ||||||||||||||||||
Waveform | Sine Wave | ||||||||||||||||||
Harmonic Distortion | THD<2% (linear load) THD<7% (nonlinear load) | ||||||||||||||||||
Output frequency | 50/60±4Hz (Sync mode) 50/60Hz±1% (Fix Freq. mode) | ||||||||||||||||||
Overload capability | 105~125%≥ 60s,126~150%≥30s The recover point is 70% | ||||||||||||||||||
Transfer time | Battery <-> Line Mode :0ms | ||||||||||||||||||
Efficiency | Line Mode | 86% | 86% | 87% | 88% | 89% | |||||||||||||
Battery Mode | 85% | ||||||||||||||||||
Communications | RS232 RS485(optional), Dry contact(optional), Network Card(Option) | ||||||||||||||||||
Alarm Function | AC/DC input under abnormal, overload condition and Inverter problems | ||||||||||||||||||
Protection Function | AC input or output above or below the range of voltage, overload, over temperature and short circuit protection | ||||||||||||||||||
Noise | <50dB | <55dB |
Subject to change according to order, check the product name plate for specified battery voltage information.