RM22010-B is a power supply device that converts standard AC voltage into stable 220Vdc for communication power supply system.
For a larger load capacity, the rectifier modules can be connected in parallel, or an additional independent monitoring module can be used for intelligent control.The rectifier module is a plug-in modular unit designed to be compatible with racks and cabinets.
Input | Single |
Input Voltage Range | 90Vac to 265Vac |
Rate input Voltage | 110Vac / 220Vac |
Normal Input | 100Vac to 240Vac |
Frequency Range | 45Hz-65Hz |
Max Input Current | 14.2A±10%@176Vac/2500W |
Surge Current | Compliant standard:ETSI300132-3 |
Efficiency | ≥93%@220Vac 100% Load |
PF | ≥0.98@220Vac100% Load |
Rate Capacity | 2500W(176Vac~265Vac) 1200W(90Vac~175Vac) |
Input fuse | L Wire ,Fuse 30A |
1.2.1Output voltage current regulation
Output Voltage | +234Vdc |
Output Voltage Regulation | 220±1Vdc |
Output Range adjustable Range | +198Vdc~+286Vdc |
Line regulation | ±0.1% |
Load regulation | ±0.5% |
Voltage precision | ±0.5% |
Current precision | ±0.5% |
Output current deviation | ≤0.5% |
Output current Regulate deviation | ≤±0.3A |
Current Sharing(176Vac~264Vac,50%~100% load) | ≤±5% |
Min- Current | 0A |
Rate current | 10A |
Peaking current | 11A |
Tempe. coefficient(1/℃) | ≤±0.02% |
Rate Capacity | 2500W(176Vac~264Vac) 1200W(90Vac~175Vac) |
Output Voltage | Ripple and Noise (Peaking-Peaking) |
+234Vdc | 2.34Vp-p@25℃;(Testing based on rate Input voltage & Output Voltage ,100% loading ) |
Note: 1) Ripple and Noise testing:Ripple and noise Default as 20 MHz.
Voltage overshoot | Adjustment slope | Loading |
+234V±5% | 0.1A/uS | 25% to 50% Load 50% to75% load |
Note:Adjustment slope Cycle 4ms。
Output Voltage | Overshoot Voltage | |
On | OFF | |
+234V | ≤5% | ≤5% |
Loading Range: Minimum to maximum.
1.2.6 Power on output delay time
Output Voltage | 220Vac@25℃ |
+198V~+286V | 3S~8S |
The power LED is installed on the power panel side and the output status is shown in the table below.
Indicator | LED Color | Normal Status | abnormal status | Abnormal Reasons |
Power running indicators | Green | ON | OFF | Mains fault(No AC input, AC input under voltage)or Auxiliary power abnormal . |
Protect indicators | Yellow | OFF | ON | AC Input Over-Voltage;Operation Environment or Rectifier over-temperature;Communication Fault;Output Under Voltage;Output Short circuit. |
Fault Indicator | Red | OFF | ON | Output Over-voltage |
OFF | FLASH | Fans Fail | ||
Note:Rectifier module under Manual Operation,,Green LED will be Flash |
The module alarm information is flashed in real time on the LED in the form of a fault code. The fault code is shown in the following table.
Fault Code | Code Meaning |
E31 | Output Under Voltage |
E32 | Rectifier module over-temp. |
E33 | AC Under-voltage |
E36 | Output Over voltage |
E38 | Fans Fault |
1.2.9 Communication function of Rectifier and Monitor Control Module
Rs485 Interface , Rectifier module and Monitor control Module
The 485 interface of the rectifier module application with isolated 。
Main function of Rectifier module communication :
1、Remote communication
The module's protection signals (input fault, over temperature, output overvoltage, over-current, etc.) and fault signals will be transmitted to the monitoring unit.
2、Remote detection
Detect rectifier module output Voltage /Current will be reports to Monitor module
3、Remote control
According to the monitor Control Module Orders,Control Rectifier module ON/OFF, Float Charge and Equ--charge and Charge switching.
4、Remote adjust
According to the monitor control module orders , adjust rectifier module output Voltage,and adjust the Output current limited current point between 10%~ 100% .
1.3.1 Output Limited Current Protection
Output Voltage | Current Limited Point | Note |
+234V | 11A | Limited Current Output |
1.3.2 Output Circuit Protection
Output Voltage | Note |
+234V | Short circuit current limit 2A,After the fault release, the output voltage will be recovered |
Output Voltage | Default Protection Point |
+234 | 290±5V. (Three times Over voltage, Rectifier module Will be Locked ) |
Note:Under Locked Status,need to Disconnect AC Power firstly, then Connect AC power again, rectifier module will be working again )
1.3.4 Input Over Voltage Protection
Input Voltage | Note |
310±10Vac | Output Will be closed,Backlash Voltage >10V |
1.3.5 Input Under Voltage Protection
Input Voltage | Note |
80±5Vac | Recovery Voltage 90V±5V, Voltage Backlash >5V |
1.3.6 Over-Temp. Protection
Temp. | Note |
≤55℃ | Note |
55℃~65℃ | The module support maximum output power without over-temperature protection and the module running normally. |
>65℃ | The module will automatically derate to ensure a long-time stable output of at least 50% of rated power |
1.3.7 Size
H×W×D:102mm×114mm×293mm
RM22010-B is a power supply device that converts standard AC voltage into stable 220Vdc for communication power supply system.
For a larger load capacity, the rectifier modules can be connected in parallel, or an additional independent monitoring module can be used for intelligent control.The rectifier module is a plug-in modular unit designed to be compatible with racks and cabinets.
Input | Single |
Input Voltage Range | 90Vac to 265Vac |
Rate input Voltage | 110Vac / 220Vac |
Normal Input | 100Vac to 240Vac |
Frequency Range | 45Hz-65Hz |
Max Input Current | 14.2A±10%@176Vac/2500W |
Surge Current | Compliant standard:ETSI300132-3 |
Efficiency | ≥93%@220Vac 100% Load |
PF | ≥0.98@220Vac100% Load |
Rate Capacity | 2500W(176Vac~265Vac) 1200W(90Vac~175Vac) |
Input fuse | L Wire ,Fuse 30A |
1.2.1Output voltage current regulation
Output Voltage | +234Vdc |
Output Voltage Regulation | 220±1Vdc |
Output Range adjustable Range | +198Vdc~+286Vdc |
Line regulation | ±0.1% |
Load regulation | ±0.5% |
Voltage precision | ±0.5% |
Current precision | ±0.5% |
Output current deviation | ≤0.5% |
Output current Regulate deviation | ≤±0.3A |
Current Sharing(176Vac~264Vac,50%~100% load) | ≤±5% |
Min- Current | 0A |
Rate current | 10A |
Peaking current | 11A |
Tempe. coefficient(1/℃) | ≤±0.02% |
Rate Capacity | 2500W(176Vac~264Vac) 1200W(90Vac~175Vac) |
Output Voltage | Ripple and Noise (Peaking-Peaking) |
+234Vdc | 2.34Vp-p@25℃;(Testing based on rate Input voltage & Output Voltage ,100% loading ) |
Note: 1) Ripple and Noise testing:Ripple and noise Default as 20 MHz.
Voltage overshoot | Adjustment slope | Loading |
+234V±5% | 0.1A/uS | 25% to 50% Load 50% to75% load |
Note:Adjustment slope Cycle 4ms。
Output Voltage | Overshoot Voltage | |
On | OFF | |
+234V | ≤5% | ≤5% |
Loading Range: Minimum to maximum.
1.2.6 Power on output delay time
Output Voltage | 220Vac@25℃ |
+198V~+286V | 3S~8S |
The power LED is installed on the power panel side and the output status is shown in the table below.
Indicator | LED Color | Normal Status | abnormal status | Abnormal Reasons |
Power running indicators | Green | ON | OFF | Mains fault(No AC input, AC input under voltage)or Auxiliary power abnormal . |
Protect indicators | Yellow | OFF | ON | AC Input Over-Voltage;Operation Environment or Rectifier over-temperature;Communication Fault;Output Under Voltage;Output Short circuit. |
Fault Indicator | Red | OFF | ON | Output Over-voltage |
OFF | FLASH | Fans Fail | ||
Note:Rectifier module under Manual Operation,,Green LED will be Flash |
The module alarm information is flashed in real time on the LED in the form of a fault code. The fault code is shown in the following table.
Fault Code | Code Meaning |
E31 | Output Under Voltage |
E32 | Rectifier module over-temp. |
E33 | AC Under-voltage |
E36 | Output Over voltage |
E38 | Fans Fault |
1.2.9 Communication function of Rectifier and Monitor Control Module
Rs485 Interface , Rectifier module and Monitor control Module
The 485 interface of the rectifier module application with isolated 。
Main function of Rectifier module communication :
1、Remote communication
The module's protection signals (input fault, over temperature, output overvoltage, over-current, etc.) and fault signals will be transmitted to the monitoring unit.
2、Remote detection
Detect rectifier module output Voltage /Current will be reports to Monitor module
3、Remote control
According to the monitor Control Module Orders,Control Rectifier module ON/OFF, Float Charge and Equ--charge and Charge switching.
4、Remote adjust
According to the monitor control module orders , adjust rectifier module output Voltage,and adjust the Output current limited current point between 10%~ 100% .
1.3.1 Output Limited Current Protection
Output Voltage | Current Limited Point | Note |
+234V | 11A | Limited Current Output |
1.3.2 Output Circuit Protection
Output Voltage | Note |
+234V | Short circuit current limit 2A,After the fault release, the output voltage will be recovered |
Output Voltage | Default Protection Point |
+234 | 290±5V. (Three times Over voltage, Rectifier module Will be Locked ) |
Note:Under Locked Status,need to Disconnect AC Power firstly, then Connect AC power again, rectifier module will be working again )
1.3.4 Input Over Voltage Protection
Input Voltage | Note |
310±10Vac | Output Will be closed,Backlash Voltage >10V |
1.3.5 Input Under Voltage Protection
Input Voltage | Note |
80±5Vac | Recovery Voltage 90V±5V, Voltage Backlash >5V |
1.3.6 Over-Temp. Protection
Temp. | Note |
≤55℃ | Note |
55℃~65℃ | The module support maximum output power without over-temperature protection and the module running normally. |
>65℃ | The module will automatically derate to ensure a long-time stable output of at least 50% of rated power |
1.3.7 Size
H×W×D:102mm×114mm×293mm