RM22020-B2 is a power supply device that converts 3phase 380V AC voltage into stable 220Vdc for communication power supply system.
For a larger load capacity, the rectifier modules can be connected in parallel, or an additional independent monitoring module can be used for intelligent control.The rectifier module is a plug-in modular unit designed to be compatible with racks and cabinets.
Input voltage range | 323Vac to 437Vac,max=475Vac |
Power Factor | > 0.93 @ full load |
Frequency range | 50Hz/60Hz±5% |
Inrush current | 15Atyp peak, 323Vac; 20Atyp peak, 475Vac |
Efficiency | 93%min @380Vac full load |
Harmonic current | ≥30% |
Start time | 3~10s |
Output Voltage | Regulation | Rated current | MAX current | Stabilization accuracy |
198V~286V | ±0.5% | 20.0A | 22A | ±1% |
Note: Input voltage range is three-phase 323~437 Vac
Output Voltage | Ripple & Noise (Max.) |
198V~286V | 0.5% effective value;1% peak value |
Note: 1) Measurements shall be made with an oscilloscope with 20MHz bandwidth.
2) Input voltage range is three-phase 323~437 Vac
Table 4. Test condition.
Voltage Tolerance Limit | Slew Rate | Load Change |
±5% | 0.2A/uS | 25% to 50% load and 50% to 75% |
Note: Transient response measurements shall be made with a load changing repetition rate of 50Hz to 10kHz.
198V~286V Over shoot voltage(V) | |
Turn on | Turn off |
5% | 5% |
Note: All of dc output current from Min. to Max.
Output Voltage | 380Vac input &Full Load |
234V | 3S-10S |
Note: The output voltages shall rise from10% to 90% of their output voltage.
Limit voltage | Comments |
198~286VDC | Continuously adjustable |
Limit current | Comments |
2~22A | Continuously adjustable |
The equalization current unbalance is less than 5% in the output 50% to 100% load range.
1、Telecommunication
Transmit the protection signals (AC over-under-voltage, phase loss, over-temperature, output over-voltage, over-current and other signals) and fault signals of the module to the monitoring unit.
2、Telemetry
Measure the output voltage and current of the module and report to the monitoring unit.
3、Remote control
According to the command of the monitoring unit, control the ON/OFF of the charging module, both float charging conversion.
4、Remote control
Adjust the output voltage of the module according to the command of the monitoring unit, and adjust the current limit point of the output power within the range of 10% to 100%.
Max. Over Voltage | Comments |
293V±6V | Over-voltage more than 3 times in 1 minute, output lockout, software protection point |
Note: If the power system enters a faulty open loop state, the output overvoltage protection point does not exceed 330V
Output short protection |
After short circuit, constant current 2A |
Over voltage | Recovery |
485±10vac | 460±15vac Resumption |
Under voltage | Recovery |
303±10vac | 323±15vac Resumption |
Note:3phase 323V AC ~ 437V AC
The module has phase loss protection function, when phase loss, the module half-load output.
The module is automatically protected when the temperature of the module exceeds the set value, and when the temperature decreases, the module automatically recovers.
Output Voltage | Min. Voltage | Comments |
234V | 195V±1V | 195±1V Monitor and report |
Control fan rotation according to the output current and temperature.
Detecting the working status of the fan and warning of faults
Input To Output | DC1000V 10MΩmin (at room temperature) |
Input To FG | DC1000V 10MΩmin (at room temperature) |
Output To FG | DC1000V 10MΩmin (at room temperature) |
Input To Output | 2828Vdc No breakdown and flashover |
Input To FG | 2828Vdc No breakdown and flashover |
Output To FG | 2828Vdc No breakdown and flashover |
without safety certification requirements.
The power supply shall compliance with the following Criterion:
*EN55022, CLASS A
*GB9254, CLASS A
*FCC PART15 CLASS A
*EN55022, CLASS A
*GB9254, CLASS A
*FCC PART15 CLASS A
The power supply shall compliance with the following Criterion:
* GB17626.2-1998 Chapter 5 specifies test level 3
* GB17626.2-1998
*GB17626.4-1998 Chapter 5 specifies test level 3
*GB17626.4-1998
*GB17626.5-1999 Chapter 5 specifies test level 3
*GB17626.5-1999
*GB17626.6-1998 Chapter 5 specifies test level 3
*GB17626.6-1998
*GB17626.8-1998 Chapter 5 specifies test level 4
*GB17626.8-1998
*GB17626.10-1998 Chapter 5 specifies test level 3
*GB17626.10-1998/
*GB17626.3-1998 Chapter 5 specifies test level 3
*GB17626.3-1998/
*GB17626.12-1998 1M and 100KHz oscillating wave immunity test of test level 3 as specified in Chapter 5.
*GB17626.12-1998/
* Operating: -10℃ to +40℃.
40~60℃Linearly derated to 20% of output load
* Store: - 25℃ to +55℃.
* Operating: From 10%to90% relative humidity (non-condensing).
* Store: From 5 to 95% relative humidity (non-condensing).
* Operating: to10,000 ft.
* Store: to 20,000ft.
Forced air-cooling
* <55Db @ 234V/20A 25℃
NAME | Aperture | Characteristics |
AC input | 27(U) | AC power input of the module, the input method is three-phase three-wire system, independent of phase sequence |
28(V) | ||
29(W) | ||
DC Output | 1,3 (OUT+) | DC output of the module, isolation between input and enclosure |
2,4 (OUT-) | ||
preserve | 26 (PE) | Protective earth lead of the module, internally already connected to the module housing |
averages | 10 (SHARE-) | Averages- |
7 (SHARE+) | Averages+ | |
communication interface | 16(485B) | Weak signal terminal, the communication interface between the module and the superior equipment, serial asynchronous transmission mode, the communication mode is 485 bus mode |
19(485A) |
Output Load Board Interface Diagram
7 Indicator light
There are 3 indicators on the module panel, the power indicator (green), the protection indicator (yellow) and the fault indicator (red), and their functions are shown in the table below:
indicator lamp | normal state | anomalous state | Reason for abnormality |
Power indicator (green) | clear | drown | No input voltage to the extent that the module's internal auxiliary power supply does not operate |
Protection indicator (yellow) | drown | clear | AC input over-under-voltage; |
Over temperature; | |||
Fault indicator (red) | drown | clear | Output over voltage; |
drown | Fan failure; | ||
Note: Green light blinks when the module is in manual mode |
RM22020-B2 is a power supply device that converts 3phase 380V AC voltage into stable 220Vdc for communication power supply system.
For a larger load capacity, the rectifier modules can be connected in parallel, or an additional independent monitoring module can be used for intelligent control.The rectifier module is a plug-in modular unit designed to be compatible with racks and cabinets.
Input voltage range | 323Vac to 437Vac,max=475Vac |
Power Factor | > 0.93 @ full load |
Frequency range | 50Hz/60Hz±5% |
Inrush current | 15Atyp peak, 323Vac; 20Atyp peak, 475Vac |
Efficiency | 93%min @380Vac full load |
Harmonic current | ≥30% |
Start time | 3~10s |
Output Voltage | Regulation | Rated current | MAX current | Stabilization accuracy |
198V~286V | ±0.5% | 20.0A | 22A | ±1% |
Note: Input voltage range is three-phase 323~437 Vac
Output Voltage | Ripple & Noise (Max.) |
198V~286V | 0.5% effective value;1% peak value |
Note: 1) Measurements shall be made with an oscilloscope with 20MHz bandwidth.
2) Input voltage range is three-phase 323~437 Vac
Table 4. Test condition.
Voltage Tolerance Limit | Slew Rate | Load Change |
±5% | 0.2A/uS | 25% to 50% load and 50% to 75% |
Note: Transient response measurements shall be made with a load changing repetition rate of 50Hz to 10kHz.
198V~286V Over shoot voltage(V) | |
Turn on | Turn off |
5% | 5% |
Note: All of dc output current from Min. to Max.
Output Voltage | 380Vac input &Full Load |
234V | 3S-10S |
Note: The output voltages shall rise from10% to 90% of their output voltage.
Limit voltage | Comments |
198~286VDC | Continuously adjustable |
Limit current | Comments |
2~22A | Continuously adjustable |
The equalization current unbalance is less than 5% in the output 50% to 100% load range.
1、Telecommunication
Transmit the protection signals (AC over-under-voltage, phase loss, over-temperature, output over-voltage, over-current and other signals) and fault signals of the module to the monitoring unit.
2、Telemetry
Measure the output voltage and current of the module and report to the monitoring unit.
3、Remote control
According to the command of the monitoring unit, control the ON/OFF of the charging module, both float charging conversion.
4、Remote control
Adjust the output voltage of the module according to the command of the monitoring unit, and adjust the current limit point of the output power within the range of 10% to 100%.
Max. Over Voltage | Comments |
293V±6V | Over-voltage more than 3 times in 1 minute, output lockout, software protection point |
Note: If the power system enters a faulty open loop state, the output overvoltage protection point does not exceed 330V
Output short protection |
After short circuit, constant current 2A |
Over voltage | Recovery |
485±10vac | 460±15vac Resumption |
Under voltage | Recovery |
303±10vac | 323±15vac Resumption |
Note:3phase 323V AC ~ 437V AC
The module has phase loss protection function, when phase loss, the module half-load output.
The module is automatically protected when the temperature of the module exceeds the set value, and when the temperature decreases, the module automatically recovers.
Output Voltage | Min. Voltage | Comments |
234V | 195V±1V | 195±1V Monitor and report |
Control fan rotation according to the output current and temperature.
Detecting the working status of the fan and warning of faults
Input To Output | DC1000V 10MΩmin (at room temperature) |
Input To FG | DC1000V 10MΩmin (at room temperature) |
Output To FG | DC1000V 10MΩmin (at room temperature) |
Input To Output | 2828Vdc No breakdown and flashover |
Input To FG | 2828Vdc No breakdown and flashover |
Output To FG | 2828Vdc No breakdown and flashover |
without safety certification requirements.
The power supply shall compliance with the following Criterion:
*EN55022, CLASS A
*GB9254, CLASS A
*FCC PART15 CLASS A
*EN55022, CLASS A
*GB9254, CLASS A
*FCC PART15 CLASS A
The power supply shall compliance with the following Criterion:
* GB17626.2-1998 Chapter 5 specifies test level 3
* GB17626.2-1998
*GB17626.4-1998 Chapter 5 specifies test level 3
*GB17626.4-1998
*GB17626.5-1999 Chapter 5 specifies test level 3
*GB17626.5-1999
*GB17626.6-1998 Chapter 5 specifies test level 3
*GB17626.6-1998
*GB17626.8-1998 Chapter 5 specifies test level 4
*GB17626.8-1998
*GB17626.10-1998 Chapter 5 specifies test level 3
*GB17626.10-1998/
*GB17626.3-1998 Chapter 5 specifies test level 3
*GB17626.3-1998/
*GB17626.12-1998 1M and 100KHz oscillating wave immunity test of test level 3 as specified in Chapter 5.
*GB17626.12-1998/
* Operating: -10℃ to +40℃.
40~60℃Linearly derated to 20% of output load
* Store: - 25℃ to +55℃.
* Operating: From 10%to90% relative humidity (non-condensing).
* Store: From 5 to 95% relative humidity (non-condensing).
* Operating: to10,000 ft.
* Store: to 20,000ft.
Forced air-cooling
* <55Db @ 234V/20A 25℃
NAME | Aperture | Characteristics |
AC input | 27(U) | AC power input of the module, the input method is three-phase three-wire system, independent of phase sequence |
28(V) | ||
29(W) | ||
DC Output | 1,3 (OUT+) | DC output of the module, isolation between input and enclosure |
2,4 (OUT-) | ||
preserve | 26 (PE) | Protective earth lead of the module, internally already connected to the module housing |
averages | 10 (SHARE-) | Averages- |
7 (SHARE+) | Averages+ | |
communication interface | 16(485B) | Weak signal terminal, the communication interface between the module and the superior equipment, serial asynchronous transmission mode, the communication mode is 485 bus mode |
19(485A) |
Output Load Board Interface Diagram
7 Indicator light
There are 3 indicators on the module panel, the power indicator (green), the protection indicator (yellow) and the fault indicator (red), and their functions are shown in the table below:
indicator lamp | normal state | anomalous state | Reason for abnormality |
Power indicator (green) | clear | drown | No input voltage to the extent that the module's internal auxiliary power supply does not operate |
Protection indicator (yellow) | drown | clear | AC input over-under-voltage; |
Over temperature; | |||
Fault indicator (red) | drown | clear | Output over voltage; |
drown | Fan failure; | ||
Note: Green light blinks when the module is in manual mode |