Lithium online High Frequency tower UPS

  • 1~3kva

Availability:

Online UPS Summary

An Online UPS output is independent of voltage and frequency variations of the mains.

  • Offers the highest level of critical load protection as the load is supplied with closely regulated power at all times

  • Has a load break of less than 5ms when transferring between inverter and bypass


  • Is totally transparent to the load in the case of a mains failure

  • Is the most expensive capital cost of UPS systems

  • Has a higher running cost than other types of system, as the rectifier and inverter are permanently on load.



Features:

1. The overall efficiency is as high as 98%; Provide ECO mode, achieving efficiency of over 99% and reducing power loss of UPS.

2. Design to meet the requirements of the power grid and provide a wide input voltage range of 210VAC~475VAC. Suitable for harsh power grid environments. The excellent input frequency range enables UPS to adapt to different power supply devices such as generators.

3. IGBT frequency modulation intelligent rectification and inversion technology, with an input power factor of up to 0.99 and input current harmonics as low as 3%; The output voltage and current performance are more excellent.

4. Powerful overload capacity: 110-125% load can operate normally for 10 minutes; 125-150% load can operate normally for 1 minute. And has the ability to output short circuit protection.

Model definition:


model definition

Parameters:


Model

HSS1101LT

HSS1101LST

HSS1102LT

HSS1102LST

HSS1103LT

HSS1103LST

Capacity

VA/W

1kVA/900W

2kVA/1.8kW

3kVA/2.7kW

Topology

Double Conversion Online UPS

Phase

Single Phase Input Single Phase Output

Mains Input

Wiring

L/N+PE

Rated Voltage

208/220/230/240VAC

Voltage Range

90~300VAC

Frequency Range

40Hz-70Hz

Input Power Factor

≥0.99

AC Output

Wiring

L/N+PE

Output Voltage

208/220/230/240VAC

Voltage Regulation

±1%

Output Frequency

50/60±4Hz(Sync Mode) / 50/60Hz±0.1%(Free Run)

Waveform

Sine Wave

Distortion

(THDV%)

<2%(Linear Load)


<8%(None-Linear Load)

Over load capability

100%~105% continuous.

60Sec.@105%~130% Rated Load

10Sec.@130%~150% Rated Load

0.3Sec.@>150%Rated Load

Efficiency

Line Mode

90%

91%

92%

Battery Mode

87%

88%

89%

Battery

&

Charger

Rated Battery Voltage

48/51.2VDC (default for 15/16cell of LiFePO4 )

Battery Capacity

615WH

External Battery Depends

920WH

External Battery Depends

1250WH

External Battery Depends

Backup Time

>30mins @ Full Load


>20mins @ Full Load


>20mins @ Full Load


Backup Time 2

(External Battery Module)

51.2V30AH-90mins

51.2V50AH-150mins

51.2V100AH-300mins

@ Full Load

51.2V30AH-45mins

51.2V50AH-75mins

51.2V100AH-150mins

@ Full Load

51.2V30AH-30mins

51.2V50AH-50mins

51.2V100AH-100mins

@ Full Load

Charging Current

Standard Model with Internal Battery:4A

Long Backup Time Model :4A / 8A(Optional)/ 16A(Optional)

Charging Voltage

56.8V(default for 16cell of LiFePO4 ) / Customized according to battery request

Charger Behavior &

Protection

CC. CV. Floating. Turn-Off 4 states

3 over voltage protection loop, preserve interface for over temperature/over pressure switch off interface

Physical

Chassis Style

 Tower  

Rack Dimension

1K: 438x88(2U)X400mm

1KS: 438x88(2U)X400mm

2K: 438x88(2U)X500mm

2KS:438x88(2U)X400mm

3K: 438x88(2U)X650mm

3KS:438x88(2U)X400mm

Tower Dimension

1KS~3KS: 190×318×368mm

  1K/2K/3K:190×323×420MM

Weight(Tower)

10.8kg

7.0kg

16.5kg

7.3kg

18.0kg

7.9kg

Weight(Rack)

12.5kg

6.5kg

21.6kg

6.8kg

24.5kg

8.2kg

HMI

LED DISPLAY

Mains / battery status, Load level, battery level, Operation Mode

LCD DISPLAY with LED indicator

Input Mains Voltage, Frequency, Load level, Operation Mode, Health Status

Standards

COMMUNICATION

1. RS232 PORT/USB Card (not HID)

2. Dry Contact Interface for BMS control

3. ModBUS For BMS interface

Optional Extension Card

4. Network Card:  Support SNMP/TCP/IP for remote monitoring the UPS via Smart Phone APP, Web page,  PC Monitor Software , Support Server / NAS shutdown

5. RS485-Modbus Card,  LAN(TCP IP)-ModBUS Card,

6. Mini AS400 Relay Card

Operating Environment

Endurance

Temperature range

-10~50oC

Relative Humidity

0-98%(Non-condensing)

Acoustics Noise

<55dB @ 1 meters




Model

LSS1101LT

LSS1101LST

LSS1102LT

LSS1102LST

LSS1103LT

LSS1103LST

Capacity

VA/W

1kVA/900W

2kVA/1.8kW

3kVA/2.7kW

Topology

Double Conversion Online UPS

Phase

Single Phase Input Single Phase Output

Mains Input

Wiring

1 phase 3wires ( L / N+PE)

Rated Voltage

110/115/120/127VAC

Voltage Range

Line-Neutral: 60~145VAC

Frequency Range

40Hz~70Hz

Input Power Factor

≥0.99

AC Output

Wiring

L/N+PE

Output Voltage

110/115/120/127VAC

Voltage Regulation

±1%

Output Frequency

50/60±4Hz(Sync Mode) / 50/60Hz±0.1%(Free Run)

Waveform

Sine Wave

Distortion

(THDV%)

<2%(Linear Load)


<8%(None-Linear Load)

Over load capability

1Min@105%~125%Rated Load

30Sec.@125%~150%Rated Load

0.5Sec.@>150%Rated Load

Efficiency

AC/AC Mode

88%

89%

90%

DC/AC Mode

86%

87%

88%

Battery

&

Charger

Rated Battery Voltage

48/51.2VDC (default for 15/16cell of LiFePO4 )

Battery Capacity

615WH

External Battery Depends

920WH

External Battery Depends

1250WH

External Battery Depends

Backup Time

>30mins @ Full Load


>20mins @ Full Load


>20mins @ Full Load


Backup Time 2

(External Battery Module)

51.2V30AH-90mins

51.2V50AH-150mins

51.2V100AH-300mins

@ Full Load

51.2V30AH-45mins

51.2V50AH-75mins

51.2V100AH-150mins

@ Full Load

51.2V30AH-30mins

51.2V50AH-50mins

51.2V100AH-100mins

@ Full Load

Charging Current

Standard Model with Internal Battery:4A

Long Backup Time Model :4A / 8A(Optional)/ 16A(Optional)

Charging Voltage

56.5V(default for 16cell of LiFePO4 ) / Customized according to battery request

Charger Behavior &

Protection

CC. CV. Floating. Turn-Off 4 states

3 over voltage protection loop, preserve interface for over temperature/over pressure switch off interface

Physical

Chassis Style

 Tower   

Rack Dimension

1K: 438x88(2U)X400mm

1KS: 438x88(2U)X400mm

2K: 438x88(2U)X500mm

2KS:438x88(2U)X400mm

3K: 438x88(2U)X650mm

3KS:438x88(2U)X400mm

Tower Dimension

1KS~3KS: 190×323×368MM

  1K~3K:190×323×420MM

Weight(Tower)

10.8kg

5.0kg

16.5kg

5.5kg

18.0kg

7.9kg

Weight(Rack)

12.5kg

6.5kg

21.6kg

6.8kg

24.5kg

8.2kg

HMI

LED DISPLAY

Mains / battery status, Load level, battery level, Operation Mode

LCD DISPLAY with LED indicator

Input Mains Voltage, Frequency, Load level, Operation Mode, Health Status

Standards

COMMUNICATION

1. RS232 PORT/USB Card (not HID)

2. Dry Contact Interface for BMS control

3. ModBUS For BMS interface

Optional Extension Card

4. Network Card:  Support SNMP/TCP/IP for remote monitoring the UPS via Smart Phone APP, Web page,  PC Monitor Software , Support Server / NAS shutdown

5. RS485-Modbus Card,  LAN(TCP IP)-ModBUS Card,

6. Mini AS400 Relay Card

Operating Environment

Endurance

Temperature range

-10~50oC

Relative Humidity

0-98%(Non-condensing)

Acoustics Noise

<55dB @ 1 meters

front panel   back panel


Previous: 
Next: 

ABOUT NASN

GUANGZHOU NASN POWER CO.,LTD is a professional EV charger, DC power supply and battery storage solution provider and enterprise in China, a wholly owned subsidy of NASN ELECTRONICS (HONGKONG) CO., LIMITED.

QUICK LINKS

PRODUCT CATEGORY

CONTACT US

   Contact person : Florence
   Tell : +86-20-86857678
    Phone : +86-135 1058 5626
    QQ : 28243245
    E-mail : info@nasn.cn
Copyright ©️ 2022 GUANGZHOU NASN POWER CO., LTD.  Technology by LeadongPrivacy Policy. Sitemap.