RM4850-A is a power supply device that converts standard AC voltage into stable 48Vdc for communication power supply system.
For a larger load capacity, the rectifier modules can be connected in parallel, or an additional independent monitoring module can be used for intelligent control.The rectifier module is a plug-in modular unit designed to be compatible with racks and cabinets.
Input | Single-phase two-wire |
Input Voltage | 90Vac to 290Vac,90Vdc to400Vdc |
Rate input Voltage | 220Vac |
Frequency Range | 45Hz-65Hz |
Max input Current | 18.5A±10%@155Vac/50A |
surge current | Compliant standard :ETSI300132-3 |
Efficiency | ≥93%@220Vac 100% Load |
PF | ≥0.99@220Vac/50A |
Leakage current | <3.5mA@264Vac |
Rate capacity | 2900W(154Vac~290Vac)(215Vdc-400Vdc) 1200W(90Vac~154Vac)(90Vdc-215Vdc) |
Input Protection | L line ,Fuse 25A |
Max Input Voltage | 320Vac(Power cannot be damaged) |
1.2 Output Feature
1.2.1Output voltage current regulation
Output Voltage | +53.5Vdc |
Output Default Voltage | +53.5±0.1Vdc |
Output Voltage adjust range | +43Vdc~+58Vdc |
Efficiency | ≥92%@220Vac 50-100% Load ≥93.2%@peak value |
Load sharing (50%~100% Loading) |
≤±5% |
Line Regulation | ±0.1% |
Load Regulation | ±0.5% |
Voltage Regulated Accuracy | ±0.6% |
Min- Current | 0A |
Rate Current | 50A |
Peaking Current | ≤55A |
Tempe. coefficient(1/℃) | ≤±0.02% |
Note: The rectifier module output current regulation and communication interruption are as follows:
1) The output current of the rectifier module can be adjusted according to the current command. The adjustment range is 1A~50A.
2) Communication fault more than 1 minute (Rectifier and Control monitor),A .Rectifier module output Voltage automatic recovery default Voltage 53.5V and limited current function not working;b.if the rectifier modules are controller by monitor and Power off, then rectifier system will power on(if the rectifier fault, it can not be turned on again)
Output Voltage | Ripple and Noise (Peaking-Peaking) |
+53.5Vdc | 200mVp-p@ 25℃,(Testing based on rate Input voltage & Output Voltage ,100% loading ) |
Note:Ripple and Noise testing:Ripple and noise Default as 20 MHz
Voltage overshoot | Load | Recover time |
+53.5V±5% | 25% ~ 50% load 50%~ 75% load |
≤200us |
Output Voltage | Overshoot Voltage | |
On | off | |
+53.5V | ≤5% | ≤5% |
Note:
Loading Range Minimum to maximum.
1.2.7 Power on output delay time
Output Voltage | 220Vac@25℃ |
+53.5V | 3S~10S |
Note: The power-on delay time is the time from AC power-on to output voltage (to 46VDC)
The power LED is installed on the power panel side and the output status is shown in the table below.
Indicator | LED Color | Normal Status | abnormal status | Abnormal Reasons |
Power running indicators | Green | On | off | |
Protect indicators | Yellow | Off | on | Temperature pre-alarm (working temperature more than 65 °C ,then over temperature shutdown); Sleep shutdown (the module only lights the protection indicator when the system is shut down, and the module does not report alarm). |
Fault Indicator | Red | Off | on | Output Over voltage power off、Fan fault、Over-Temp. Power off、Rectifier module inner fault。 |
1.2.9 Noise Voltage
Noise Voltage | Max | Note |
Phone noise weighting Voltage | ≤2mV | |
broadband noise Voltage | ≤50mV | 3.4~150KHz |
≤20mV | 0.15~30000KHz | |
Radio interference noise, or radio frequency noise | ≤5mV | 3.4~150KHz |
≤3mV | 150~200KHz | |
≤2mV | 200~500KHz | |
≤1mV | 500~30000KHz |
1.2.10 Rectifier module and monitor module communication function
RS485 communication mode (half-duplex, double-line) is adopted between the rectifier module and the monitoring module.
The RS485 interface in the rectifier module needs to be isolated. The RS485 power supply is +5Vdc (regulation accuracy ±5%), which is provided by the monitoring module.
The main monitoring information of the rectifier module is:
1) Adjust Voltage and Current function: meet the requirements of battery floating charge and meet the adjust voltage requirements;
2) Single module switch machine control;
3) Alarm information:
Mains failure: mains failure (AC input over voltage);
Module protection: temperature pre-alarm;
Module failure: Output over voltage shutdown, fan failure, over temperature shutdown or no output caused by internal causes of other modules; (module is in: sleep shutdown state, mains failure does not report module failure).
1.3.1 Output Limited Current Protection
Output Voltage | Limited Current point | Note |
+53.5V | 105%~110% | Limited current output |
1.3.2 Output short circuit Protection
Output Voltage | Note |
+53.5V | Restart after Protection |
1.3.3 Output Over Voltage Protection
Output Voltage | Protection Point |
+53.5V | 60±1V. (Lock) |
Note: After entering the lock protection state, you need to disconnect the AC power first, and then re-power on, the rectifier module can be re-operated.
1.3.4 Input Over Voltage Protection
Input Voltage | Note |
310±10Vac | Output off,Self-recovery after normal voltage |
output recovery point backlash>10V |
Note: Input overvoltage protection should be tested at 50A rated load.
1.3.5 Input under Voltage Protection
Input Voltage | Note |
80±5Vac | Output is closed. Self-recovery after normal Voltage |
Output Recovery point backlash>5V |
1.3.6 Over -Temp.Protection
Temp. | Note |
≤55℃ | With maximum output Capacity ability , without over-temperature protection and the module is running normally. |
55℃~65℃ | The module can be automatically derate to ensure long-term stable output of at least 50% of rated power |
>65℃ | Power off,After power off,Recovery temperature difference >10℃ |
RM4850-A is a power supply device that converts standard AC voltage into stable 48Vdc for communication power supply system.
For a larger load capacity, the rectifier modules can be connected in parallel, or an additional independent monitoring module can be used for intelligent control.The rectifier module is a plug-in modular unit designed to be compatible with racks and cabinets.
Input | Single-phase two-wire |
Input Voltage | 90Vac to 290Vac,90Vdc to400Vdc |
Rate input Voltage | 220Vac |
Frequency Range | 45Hz-65Hz |
Max input Current | 18.5A±10%@155Vac/50A |
surge current | Compliant standard :ETSI300132-3 |
Efficiency | ≥93%@220Vac 100% Load |
PF | ≥0.99@220Vac/50A |
Leakage current | <3.5mA@264Vac |
Rate capacity | 2900W(154Vac~290Vac)(215Vdc-400Vdc) 1200W(90Vac~154Vac)(90Vdc-215Vdc) |
Input Protection | L line ,Fuse 25A |
Max Input Voltage | 320Vac(Power cannot be damaged) |
1.2 Output Feature
1.2.1Output voltage current regulation
Output Voltage | +53.5Vdc |
Output Default Voltage | +53.5±0.1Vdc |
Output Voltage adjust range | +43Vdc~+58Vdc |
Efficiency | ≥92%@220Vac 50-100% Load ≥93.2%@peak value |
Load sharing (50%~100% Loading) |
≤±5% |
Line Regulation | ±0.1% |
Load Regulation | ±0.5% |
Voltage Regulated Accuracy | ±0.6% |
Min- Current | 0A |
Rate Current | 50A |
Peaking Current | ≤55A |
Tempe. coefficient(1/℃) | ≤±0.02% |
Note: The rectifier module output current regulation and communication interruption are as follows:
1) The output current of the rectifier module can be adjusted according to the current command. The adjustment range is 1A~50A.
2) Communication fault more than 1 minute (Rectifier and Control monitor),A .Rectifier module output Voltage automatic recovery default Voltage 53.5V and limited current function not working;b.if the rectifier modules are controller by monitor and Power off, then rectifier system will power on(if the rectifier fault, it can not be turned on again)
Output Voltage | Ripple and Noise (Peaking-Peaking) |
+53.5Vdc | 200mVp-p@ 25℃,(Testing based on rate Input voltage & Output Voltage ,100% loading ) |
Note:Ripple and Noise testing:Ripple and noise Default as 20 MHz
Voltage overshoot | Load | Recover time |
+53.5V±5% | 25% ~ 50% load 50%~ 75% load |
≤200us |
Output Voltage | Overshoot Voltage | |
On | off | |
+53.5V | ≤5% | ≤5% |
Note:
Loading Range Minimum to maximum.
1.2.7 Power on output delay time
Output Voltage | 220Vac@25℃ |
+53.5V | 3S~10S |
Note: The power-on delay time is the time from AC power-on to output voltage (to 46VDC)
The power LED is installed on the power panel side and the output status is shown in the table below.
Indicator | LED Color | Normal Status | abnormal status | Abnormal Reasons |
Power running indicators | Green | On | off | |
Protect indicators | Yellow | Off | on | Temperature pre-alarm (working temperature more than 65 °C ,then over temperature shutdown); Sleep shutdown (the module only lights the protection indicator when the system is shut down, and the module does not report alarm). |
Fault Indicator | Red | Off | on | Output Over voltage power off、Fan fault、Over-Temp. Power off、Rectifier module inner fault。 |
1.2.9 Noise Voltage
Noise Voltage | Max | Note |
Phone noise weighting Voltage | ≤2mV | |
broadband noise Voltage | ≤50mV | 3.4~150KHz |
≤20mV | 0.15~30000KHz | |
Radio interference noise, or radio frequency noise | ≤5mV | 3.4~150KHz |
≤3mV | 150~200KHz | |
≤2mV | 200~500KHz | |
≤1mV | 500~30000KHz |
1.2.10 Rectifier module and monitor module communication function
RS485 communication mode (half-duplex, double-line) is adopted between the rectifier module and the monitoring module.
The RS485 interface in the rectifier module needs to be isolated. The RS485 power supply is +5Vdc (regulation accuracy ±5%), which is provided by the monitoring module.
The main monitoring information of the rectifier module is:
1) Adjust Voltage and Current function: meet the requirements of battery floating charge and meet the adjust voltage requirements;
2) Single module switch machine control;
3) Alarm information:
Mains failure: mains failure (AC input over voltage);
Module protection: temperature pre-alarm;
Module failure: Output over voltage shutdown, fan failure, over temperature shutdown or no output caused by internal causes of other modules; (module is in: sleep shutdown state, mains failure does not report module failure).
1.3.1 Output Limited Current Protection
Output Voltage | Limited Current point | Note |
+53.5V | 105%~110% | Limited current output |
1.3.2 Output short circuit Protection
Output Voltage | Note |
+53.5V | Restart after Protection |
1.3.3 Output Over Voltage Protection
Output Voltage | Protection Point |
+53.5V | 60±1V. (Lock) |
Note: After entering the lock protection state, you need to disconnect the AC power first, and then re-power on, the rectifier module can be re-operated.
1.3.4 Input Over Voltage Protection
Input Voltage | Note |
310±10Vac | Output off,Self-recovery after normal voltage |
output recovery point backlash>10V |
Note: Input overvoltage protection should be tested at 50A rated load.
1.3.5 Input under Voltage Protection
Input Voltage | Note |
80±5Vac | Output is closed. Self-recovery after normal Voltage |
Output Recovery point backlash>5V |
1.3.6 Over -Temp.Protection
Temp. | Note |
≤55℃ | With maximum output Capacity ability , without over-temperature protection and the module is running normally. |
55℃~65℃ | The module can be automatically derate to ensure long-term stable output of at least 50% of rated power |
>65℃ | Power off,After power off,Recovery temperature difference >10℃ |