48VDC BATTERY CHARGERS/RECTIFIER 250A is designed for utility communications.
System
Switching and modular type power module,load sharing and parallel operation ,equipped with microprocessor-based digital control technology, with remote configuration and monitoring capabilities via standard communications protocol SNMPv3 including associated remote communication interface.The system includes control unit, power modules, chassis/DC rack and all necessary instrumentations
Monitoring Unit has the following functions.
1.Adjustment of relevant rectifier parameters:
§ Float § Equalize
§ Battery current limit
§ Output current limit
§ Alarm setting
2.Protect the load and battery by disconnecting and reconnecting the load and battery during output over/under voltages
3.Monitor battery temperature and adjust battery float voltage accordingly (temperature compensated charging)
4.Basic display and metering parameters:
§ Input AC voltage § DC output voltage and current
§ Battery charging/discharging voltage and current
§ Alarms and other messages
5.Minimum monitored alarms:
§ Mains fail § Rectifier module fail
§ High voltage shutdown
§ High voltage shutdown
§ Battery low voltage alarm (default: -47.0V)
§ Battery low voltage disconnect (default: -43.2V)
§ Battery high voltage alarm (default: -56.2V)
§ Battery/Output high voltage shutdown (default: -58.0V)