NASN 110vdc B series rectifier power supply B220/110-60M3, which converts AC 220V to DC 110V offer an output adjustable from 90-150Vdc.
This makes it suitable for charging 110Vdc batteries, as well making it versatile large industrial cabinets requiring tens of kilowatts. Integrated with DC earth fault auto detect function, B series 110VDC rectifier power supply can fit your different requirements.
When the voltage between the anode bus and PE is equal to the voltage between the negative electrode and PE, it indicates that the machine has good DC grounding, excellent insulation and safety, and there is no problem of ground leakage. Therefore, use your current measurement method to test whether there is DC earth fault.
MODEL | B380/110-60M3 | B380/110-120M6 | B380/110-180M9 | B380/110-300M15 | B380/110-600M30 | |
Configuration | 3pcs 110V/20A module +1pcs monitor | 6pcs 110V/20A module +1pcs monitor | 9pcs 110V/20A module +1pcs monitor | 15pcs 110V/20A module +1pcs monitor | 30pcs 110V/20A module +1pcs monitor | |
Environmental | Operating temperature | -40°C ~ 55°C | ||||
Storage temperature | -40°C ~ 70°C | |||||
Relative humidity | ≤ 90%RH (30°C) | |||||
Altitude | ≤ 2000m (derating is necessary above 2,000m) | |||||
AC Input | AC input system | L1+L2+L3+N/380Vac | ||||
Input voltage range | 323-437VAC | |||||
Input AC voltage frequency | 45Hz ~ 65Hz | |||||
Max input current | ≤28.4A | |||||
Power factor | ≥ 0.99 | |||||
DC Output | Nominal output voltage | 110VDC | ||||
Rated output voltage | 121VDC | |||||
Rated Output Capacity | 7.5kW | 15kW | 22.5kW | 37.5kW | 75kW | |
Output DC voltage | 90VDC ~ -150VDC | |||||
Output DC current | 60A | 120A | 180A | 300A | 600A | |
Voltage set-point accuracy | ≤ 1% | |||||
Efficiency | ≥ 93.2% | |||||
Noise (peak-peak) | ≤ 200mV (0 ~ 20MHz) | |||||
Weighted noise | ≤ 2mV (300Hz ~ 3400Hz) | |||||
AC Input Alarm and Protection | AC input over-voltage alarm point | Default: 280VAC ± 5VAC* | ||||
AC input under-voltage alarm point | Default: 176VAC ± 5VAC | |||||
AC input over-voltage protection recovery difference | Default: 295VAC ± 5VAC, 10VAC lower than the AC input over-voltage protection point | |||||
AC input under-voltage protection point | Default: 180VAC ± 5VAC* | |||||
DC Output Alarm And Protection | DC output over-voltage alarm point | Default:149VDC ± 0.5VDC* | ||||
DC output under-voltage alarm point | Default:90VDC ± 0.5VDC* | |||||
DC output over-voltage protection point | Default: 97.2VDC ± 0.5VDC* | |||||
LLVD | Default: 99VDC ± 0.5VDC* | |||||
BLVD | Default: 97.2VDC ± 0.5VDC* | |||||
Rectifier | Load sharing | The rectifiers can work in parallel and share the current. The unbalance is better than ± 5% rated output current. | ||||
Derated by input (at 45°C) | The rectifier can output power of 100% with input voltage of ≥154VAC; The rectifier can output power capacity 1200W with input voltage <154VAC; Rectifiers under-voltage stop with input voltage of 85VAC | |||||