NASN 220vdc A series rectifier power supply A220/220-30M3, which converts AC 220V to DC 220V offer an output adjustable from 180-300Vdc.
This makes it suitable for charging 220Vdc batteries, as well making it versatile large industrial cabinets requiring tens of kilowatts. Integrated with mobus RS232 communication, A series 220VDC rectifier power supply can fit your different requirements.
A series can be 380Vac input for 10A,20A,30A,40A,50A,60A,70A power supply.
MODEL | A220/220-10M1 | A220/220-20M2 | A220/220-30M3 | A380/220-60M6 | A380/220-70M7 | |
Configuration | 1pcs 220V/10A module +1pcs monitor | 2pcs 220V/10A module +1pcs monitor | 3pcs 220V/10A module +1pcs monitor | 6pcs 220V/10A module +1pcs monitor | 7pcs 220V/20A module +1pcs monitor | |
Environmental | Operating temperature | -40°C ~ 55°C | ||||
Storage temperature | -40°C ~ 70°C | |||||
Relative humidity | ≤ 90%RH (30°C) | |||||
Altitude | ≤ 2000m (derating is necessary above 2,000m) | |||||
AC Input | AC input system | L+N+PE/220Vac | L1+L2+L3+N/380Vac | |||
Input voltage range | 90VAC ~ 280VAC | 323-437VAC | ||||
Input AC voltage frequency | 45Hz ~ 65Hz | |||||
Max input current | ≤28.4A | |||||
Power factor | ≥ 0.99 | |||||
DC Output | Nominal output voltage | 220VDC | ||||
Rated output voltage | 242VDC | |||||
Rated Output Capacity | 2.5kW | 5kW | 7.5kW | 15kW | 17.5kW | |
Output DC voltage | 180VDC ~ -300VDC | |||||
Output DC current | 10A | 20A | 30A | 60A | 70A | |
Voltage set-point accuracy | ≤ 1% | |||||
Efficiency | ≥ 93.2% | |||||
Noise (peak-peak) | ≤ 200mV (0 ~ 20MHz) | |||||
Weighted noise | ≤ 2mV (300Hz ~ 3400Hz) | |||||
AC Input Alarm and Protection | AC input over-voltage alarm point | Default: 280VAC ± 5VAC* | ||||
AC input under-voltage alarm point | Default: 176VAC ± 5VAC | |||||
AC input over-voltage protection recovery difference | Default: 295VAC ± 5VAC, 10VAC lower than the AC input over-voltage protection point | |||||
AC input under-voltage protection point | Default: 180VAC ± 5VAC* | |||||
DC Output Alarm And Protection | DC output over-voltage alarm point | Default:298VDC ± 0.5VDC* | ||||
DC output under-voltage alarm point | Default: 180VDC ± 0.5VDC* | |||||
DC output over-voltage protection point | Default: 194.5VDC ± 0.5VDC* | |||||
LLVD | Default: 198VDC ± 0.5VDC* | |||||
BLVD | Default: 194.5VDC ± 0.5VDC* | |||||
Rectifier | Load sharing | The rectifiers can work in parallel and share the current. The unbalance is better than ± 5% rated output current. | ||||
Derated by input (at 45°C) | The rectifier can output power of 100% with input voltage of ≥154VAC; The rectifier can output power capacity 1200W with input voltage <154VAC;Rectifiers under-voltage stop with input voltage of 85VAC | |||||