Views: 0 Author: Site Editor Publish Time: 2024-02-16 Origin: Site
NASN 220Vdc rectifier power supply rectifiers system bring advanced technology to the DC power industry. Innovative engineering combines the best in efficiency and reliability to meet the power requirements for a variety of system applications. This rectifier is specifically designed to recharge all types of stationary batteries for large utility, petrochemical and industrial uses.
The fan cooled rectifier module has extremely high density providing the most power in the least amount of space. A compact shelf accommodates three to four rectifiers per 19in shelf and can be paralleled up to 5*2U 19in shelf.
Local and remote setup, adjustment and control is a simple, single-step process with the rectifier System Controller. By utilizing TCP/IP technology, complete configuration and monitoring of power equipment is possible through a Windows Internet Explorer browser.
We can provide turnkey solutions for outside plant, headend, telecommunications, industrial and renewable energy applications. We work to combine your small-, medium- and large-scale projects with the necessary installation resources.
MODEL | B380/220-30M3 | B380/220-60M6 | B380/220-90M9 | B380/220-150M15 | B380/220-300M30 | |
Configuration | 3pcs 220V/10A module +1pcs monitor | 6pcs 220V/10A module +1pcs monitor | 9pcs 220V/10A module +1pcs monitor | 15pcs 220V/10A module +1pcs monitor | 30pcs 220V/20A module +1pcs monitor | |
Environmental | Operating temperature | -40°C ~ 55°C | ||||
Storage temperature | -40°C ~ 70°C | |||||
Relative humidity | ≤ 90%RH (30°C) | |||||
Altitude | ≤ 2000m (derating is necessary above 2,000m) | |||||
AC Input | AC input system | L1+L2+L3+N/380Vac | ||||
Input voltage range | 323-437VAC | |||||
Input AC voltage frequency | 45Hz ~ 65Hz | |||||
Max input current | ≤28.4A | |||||
Power factor | ≥ 0.99 | |||||
DC Output | Nominal output voltage | 220VDC | ||||
Rated output voltage | 242VDC | |||||
Rated Output Capacity | 7.5kW | 15kW | 22.5kW | 37.5kW | 75kW | |
Output DC voltage | 180VDC ~ -300VDC | |||||
Output DC current | 30A | 60A | 90A | 150A | 300A | |
Voltage set-point accuracy | ≤ 1% | |||||
Efficiency | ≥ 93.2% | |||||
Noise (peak-peak) | ≤ 200mV (0 ~ 20MHz) | |||||
Weighted noise | ≤ 2mV (300Hz ~ 3400Hz) | |||||
AC Input Alarm and Protection | AC input over-voltage alarm point | Default: 280VAC ± 5VAC* | ||||
AC input under-voltage alarm point | Default: 176VAC ± 5VAC | |||||
AC input over-voltage protection recovery difference | Default: 295VAC ± 5VAC, 10VAC lower than the AC input over-voltage protection point | |||||
AC input under-voltage protection point | Default: 180VAC ± 5VAC* | |||||
DC Output Alarm And Protection | DC output over-voltage alarm point | Default:298VDC ± 0.5VDC* | ||||
DC output under-voltage alarm point | Default: 180VDC ± 0.5VDC* | |||||
DC output over-voltage protection point | Default: 194.5VDC ± 0.5VDC* | |||||
LLVD | Default: 198VDC ± 0.5VDC* | |||||
BLVD | Default: 194.5VDC ± 0.5VDC* | |||||
Rectifier | Load sharing | The rectifiers can work in parallel and share the current. The unbalance is better than ± 5% rated output current. | ||||
Derated by input (at 45°C) | The rectifier can output power of 100% with input voltage of ≥154VAC; The rectifier can output power capacity 1200W with input voltage <154VAC; Rectifiers under-voltage stop with input voltage of 85VAC | |||||